The BatScan Hardware

Batscan is the world's only Battery Monitoring System that fully complies with the European Low Voltage Directive (LVD) and the EN60950 safety standard for information technology equipment, even when connected to a high voltage UPS battery.

The purpose of these standards is foremost to protect buildings from fire and people from electrical chock. However, since the batteries are a very critical component in a backup-power system, extreme caution must be taken when connecting additional wires to them.

Batscan is therefore going one step further by implementing the same level of protection for the batteries. This guarantees that the monitoring system only can detect battery faults, not cause them.

A true Monitoring System
Inherently by design, Batscan cannot control the battery, the charger or the load. This is not a limitation, it is an essential requirement for a true monitoring system, that by definition only should be allowed to observe, without any means of influencing the result.

Any technical system can fail, and most do - sooner or later. When this happens with a device that controls the battery, an independent monitoring system will prove it value.

Advanced technology
Distinctive features that characterizes a Batscan as the best choice for monitoring large UPS batteries, includes but are not limited to:

  • It is Safe, for people AND batteries.
  • It measures all battery cells Simultaneously.
  • It is Fast enough to capture short events.

It seams obvious that this should be basic requirements for all Battery Monitoring Systems, but facts are that no other system feature any of this characteristics, even less all three of them.

It poses a great engineering challenge to combine these requirements into one single system, at a reasonable cost. It cannot be done like a standard "text book" data acquisition system. Fortunately, with the advanced signal processing technology that is available today, it is possible.


Protective resistor
To comply with the first 'must' requirement Batscan uses a large resistor for all connections to the battery cells. The resistor value is 2MΩ (2 000 000 ohm), and it is rated for 10kV (10 000 Volt) over voltage pulses.

This resistor creates a high impedance circuit with very low current capability, which is essential for safety. (However, the resistor also imposes some undesired side effects in terms of adding noise and making the system susceptible to EMI, which cannot be handled by a simple monitoring system.)

Batscan Protective resistor

The resistor is integrated in the battery connectors with a crimp splice for the measuring leads and a FAST-ON connector that mates with a tab-washer fitted on the cell terminals.

Low Current High Current  
    Quick Connect Tab for M8 Connection to battery terminal - Click for a high resolution picture
Batscan Protective resistor assembly
   
Current limiting resistor    

The wiring harness in a Batscan system impose no risk for hazards, the resistor limits the maximum short circuit current to 250µA (0.00025 A) at 500V, this current is not enough to cause a spark, discharge the battery or hurt a person.


Intelligent measuring modules
The real workhorses in the Batscan system are the measuring modules. They use a dual processor digital signal processing (DSP) technique to restore the DC signal from the batteries with high speed oversampling digital to analog conversions followed by a property filtering algorithm. An internal transformer with reinforced isolation (6kV test voltage) separates the analog side from the communication bus.

Low Voltage High Voltage
Digital post-processing
& bus interface
Analog front-end with
high speed sampling
Temperature Connections
to Battery
Network In
Network Out
  →   ←  
  6kV Test Voltage  

There are two types of measuring modules, one that measures up to 8 cell (or block voltages) via the protective resistors, and one that measures up to 4 string currents via hall-effect current transducers.

Each module also measures internal on-board temperature and allows for up to 8 external temperature sensors to be connected.

All modules are powered from the communication bus.


Modular design
The modular design allows for flexible configuration and system layout. The modules can be mounted directly on the battery, inside the wire conduits, grouped together in larger enclosures or even be placed in a 19" rack cabinet.

For large UPS batteries, a common configuration is wall mounted IP65 enclosures with 4 to 10 modules placed next to each battery string.

The modules are interconnected with modular cable and plugs, for longer distances a high quality DeviceNet cable is used.


BNIF: PC Interface
Adapter


BA642: 4-channel
Current measuring
module


BA643: 8-channel
Voltage measuring
module

 



Batscan hardware with wiring to a 24-cell (48V) telecom battery.
 


All battery connections have integrated protective resistors.
 


Batscan in a large UPS installation monitoring 7 batteries with a total of 5136 cells.
 


The Batscan measuring modules placed in wall-mounted IP65 enclosures.
 


Batscan protective resistors connected to wire taps supplied by battery manufacturer.
 


Current transducer clamped onto an intertier cable.
 


Faulty battery cells are immediately detected by Batscan, when replaced the full battery capacity is restored.