Batscan − Technical Specifications
General System Overall
Bus Network | Value | Unit | Note | Condition
|
---|
Max cable segments (Sub Networks) | 240 | | | bus/star topology
| Max hierarchical levels | 4 | | |
| Max total number of nodes | 2404 | | 1, 2 |
| Signaling interface | RS485 | | |
| Communication protocol | Proprietary | | |
| Min transmission rate | 115200 | b/s | |
| Max transmission rate | 2 | Mb/s | |
|
| Bus Network Segment | Value | Unit | Note | Condition
|
---|
Max cable length vs cable type | 1000 | m | | Belden 3082A
| 500 | | Belden 3084A
| 200 | | Modular-6 (RJ12)
| 100 | | Modular-4 (RJ11)
| Max distributed Power | 15 | W | |
| Max distributed Voltage | 16 | V | |
| Max distributed Current | 1.5 | A | |
| Max number of nodes | 240 | | 2 |
|
Notes: | 1. addressable units, practically limited to distributed power suppy.
|
---|
| 2. nodes = Data Acquisition Modules or Sub-Networks.
|
---|
Computer Interface & Data Acquisition Modules
All modules | Value | Unit | Note | Condition
|
---|
Isolation voltage | ±4 | kV | |
| ±6 | | -HV version
| Measured temperature resolution | 0.5 | °C | |
| Operating temperature range | +10 − +40 | °C | |
| Time resolution | 10 | µs | 1 |
| Power supply voltage range | 6 to 16 | V | |
|
| Block Voltage Modules BA673 | Value | Unit | Note | Condition
|
---|
Measured block/cell voltage channels | 8 | | | in series
| Probe resistance | 2 | MΩ | 2 |
| Differential input impedance | 6 | MΩ | 3 |
| Max measuring current | ±20 | µA | | 8 x 15 V
| Measuring voltage range | ±20 | V | |
| Measuring accuracy | ±0.1 | % | 4 |
| Measured voltage resolution | 1 | mV | |
| Continuous common mode voltage | ±500 | V | |
| ±800 | | -HV version
| Continuous over-voltage | ±3 | kV | |
| Peak over-voltage | ±10 | kV | | 10µs pulse
| Power supply current | 2 | mA | |
|
| String Current Modules BA672-CT | Value | Unit | Note | Condition
|
---|
Measured string current channels | 4 | | |
| Input impedance | 1 | MΩ | |
| Measuring voltage range | ±12 | V | 5 |
| Measuring accuracy | ±0.1 | % | 4, 6 |
| Power supply current | 30 | mA | | + 50mA/CT
|
Notes: | 1. Using 240 x over-sampling.
|
---|
| 2. The probe resistor is integrated in terminal connector.
|
---|
| 3. Including probe resistance.
|
---|
| 4. After calibration.
|
---|
| 5. Output voltage from current transducer is ± 5V at nominal (FS) current.
|
---|
| 6. Not including error from current transducer (typical 1%FS).
|
---|
All specifications are subject to change without notice.
|