Battery Monitoring
      
      A battery is dependent on all of its cells.
       
      The only way of controlling each cell in a battery is to have a battery 
      monitoring system that continuously measures total current and individual 
      cell voltage. In any in case of a deviation greater than a certain value 
      the battery monitoring system should send an alarm signal. With such a 
      system any failing cell can be identified at an early stage and by replacing 
      that individual cell further damage is avoided. This method will guarantee 
      the battery’s health through its whole life cycle.
       
      
        
        
          A UPS battery is usually in one of three states:
         |  
        
  |  
         
          | 1. Float charge | 
          
             This is the most common state. In some cases, it 
              can even turn out to be the only state. The battery is charged with 
              a low current equivalent to its self-discharge with a certain margin 
              added. 
           | 
         
         
          | 2. Discharging | 
          
             When the battery 
              is supporting a load due to a power outage. In this state the battery 
              is discharged with a high current for a short period of time. The 
              current could be -(4 × C10) Amp during 10 min. 
           | 
         
         
          | 3. Recharging | 
          
             When the battery 
              is recharged after a period of discharging. In most cases the battery 
              is recharged with an increased voltage during a certain amount of 
              time, for example 24h. The current is usually limited to +(0.2 × 
              C10) A. 
             | 
         
        
  |  
         
          | 
             Note: The term C10 refers to a battery's nominal capacity in Ah, when discharged 
               during 10h to a final voltage of 1.8V per cell.
             
             | 
         
       
        
      Discharging battery cells connected in series.
      
        When discharged a battery must continuously generate a certain amount 
        of current and voltage in order for supported equipment such as an UPS 
        to work properly. A battery's terminal voltage is the sum of the cell's 
        unloaded voltage, EMF, minus its inner- and connecting lines' resistance 
        multiplied by the current. Therefore, terminal voltage drops as a result 
        of an increased current. A defect cell usually has higher internal resistance 
        resulting in lower terminal voltage than other cells in the same battery. 
       
      At high load current it is fairly easy to detect a defect cell by measuring
        voltage on each cell or block of cells. However, this requires that each
        cell's voltage is measured simultaneously. With a battery monitoring system
        that stores measurement values and compares new values with historical data
        very small variations in a cell's internal resistance can be identified well
        before the cell is ruined.
       
        
      Charging battery cells connected in series.
      
        A battery containing a number of cells connected in series is recharged 
        using a voltage recommended by the manufacturer multiplied with the number 
        of connected cells. 
      Fig.1 below shows a battery with 4 cells charged with 
        2.25 per cell, a total of 9 volt. Total voltage and average cell voltage 
        is generated by the charger. However no cell has recommended recharge 
        voltage of 2.25 volt. Therefore, the battery manufacturer has stated the 
        maximum amount a cell's voltage is allowed to deviate from the average. 
        This value is usually +-0.10V which in this case means that each cell's 
        voltage must be between 2.15 and 2.35 volt. 
      
        
       
      Fig1. Battery with normal cell voltage. 
        
      Fig.2 below shows the same battery with a defect in cell 
        #3 resulting in an increased internal resistance. An increased internal 
        resistance results in an increased cell voltage, in this case 0.3 volt. 
        This means that the other cells' voltage drops with 0.1 volt. The water 
        in Cell #3 is transformed into explosive hydrogen gas. In case this problem 
        is not discovered also cell #1 and cell #4 will fail as a result of low 
        charging voltage. Furthermore, low charging voltage will result in the 
        formation of highly insoluble lead. The water in cell #3 is transformed 
        into explosive hydrogen gas. In case this problem is not discovered, cell 
         #1 and cell #4 will also fail as a result of low charging voltage. Furthermore, 
        low charging voltage will result in the formation of highly insoluble 
        lead sulphate on the cell plates. Cell #2 will stay unaffected until all 
        water in cell #3 is consumed. 
      
          
       
      Fig2. An increased cell voltage results in decreased voltage over remaining cells. 
        
      In this particular case a Battery Monitoring System would 
        trigger an alarm as soon as voltage over cell #3 exceeds 2.35 Volt. 
      During maintenance 
        charging it is difficult to discover individual failing cells when reviewing 
        data from more than one cell per channel. If the cells in Fig. 2 are grouped 
        in pairs, average voltage in group 1 (cells #1 and #2) is 2.15 Volt and 
        in group 2 (cells #3 and #4) 2.35 Volt. Both these values are within limit. 
        
      Conclusion
      
        - Measuring 
            a battery’s total voltage does not give any information about 
            the state of health of individual battery cells.          
        
 - Measuring 
            voltage over a group of cells gives only an average value for each 
            cell within the group.       
        
 - Measuring each individual cell is the only way to guarantee that each cell is receiving the correct voltage.
      
  
      
     |